UK GENERATOR SPECIALISTS · WORLDWIDE EXPORT
About FW PowerPower calculatorKnowledge centre01829 863497
Used generator · FWC003

1500 kVA Shenton Perkins 4012-46TWG3A Acoustic Diesel Generator – 2024

FWC003 Shenton generator secured to a flatbed trailer in the FW Power yard

At a glance

Power (kVA)
1360 prime / 1500 standby
Engine
Perkins 4012-46TWG3A V12
Year
2024
Hours run
Test Hours Only
Voltage
400 / 230 V
Phase
3

Test Hours Only.

Available. One generator in this listing. Price on enquiry.

Enquire about this generatorSpeak to our team: 01829 863497Download datasheet

Overview

  • 2024 Shenton PHG1500Pe acoustic diesel generator, available as one unit under stock reference FWC003. Price on application.
  • 1360 kVA / 1088 kW prime output and 1500 kVA / 1200 kW standby output.
  • Perkins 4012-46TWG3A V12 diesel engine coupled to a Stamford S6L1D-H41 alternator.
  • 400 / 230 V, 50 Hz, three phase and 1500 rpm.
  • Acoustic, weather-resistant enclosure with an integral 2500-litre fuel tank.
  • Test Hours Only.

1500 kVA Perkins diesel generator for sale

FW Power Generators offers this 2024 Shenton PHG1500Pe acoustic diesel generator for demanding commercial, industrial and critical standby power applications.

The Perkins 4012-46TWG3A is a heavy-duty 45.5-litre V12 diesel engine, operating at 1500 rpm with turbocharging, water-cooled aftercooling and electronic governing. It is coupled to a genuine Stamford S6L1D-H41 synchronous alternator.

With 1360 kVA prime and 1500 kVA standby output, the set can support extended operation under varying load or emergency power during a mains failure, subject to the required duty and site specification.

The substantial acoustic enclosure and integral fuel tank provide a practical package for a permanent installation. Its 2024 manufacture and Perkins / Stamford combination offer an alternative to ordering a new high-capacity generating set.

UK delivery and worldwide export are available. Contact FW Power for a quotation, inspection appointment and confirmation of the specification for your project.

Key features

  • Heavy-duty industrial construction and acoustic, weather-resistant enclosure
  • Perkins V12 engine with turbocharging and water-cooled aftercooling
  • Electronic engine governing
  • Stamford S6L1D-H41 alternator
  • 2500-litre integral diesel fuel tank
  • Suitable for automatic mains-failure applications
  • Large-capacity output circuit breaker
  • Digital generator control and monitoring system
  • Battery starting system, engine coolant heater and battery charging system
  • Emergency stop and engine / alternator protection
  • Suitable for permanent standby or prime-power installations

Applications

Suitable applications include data centres, manufacturing facilities, hospitals and healthcare, distribution centres, warehouses, telecommunications, commercial buildings, industrial facilities, construction projects, critical infrastructure, emergency standby power, large UPS-supported installations and export power projects. Final selection depends on the site load and operating duty.

Inspection and testing

Inspection is available by prior appointment. A full-load bank test and witness testing can be arranged on request.

FW Power can also provide pre-delivery inspection, servicing, commissioning, installation, ATS and control systems, fuel systems, generator maintenance contracts, UK delivery and worldwide export support. Contact the team to agree the scope and quotation.

Delivery and export

FW Power can arrange delivery throughout the United Kingdom and assist with worldwide export and shipping. Contact the team regarding export documentation, port delivery, loading, container or RoRo shipping, customs documentation, commercial invoices and Bills of Lading.

Tell us your delivery location, access and offloading facilities so we can quote the transport requirements. Shipping arrangements and equipment suitability are confirmed for each project.

Enquire about FWC003

Adam Lavin · Sales Director

+44 7424 980523 · WhatsApp · Adam@fwpower.co.uk

Subject to prior sale.

Quote reference FWC003 when enquiring about this generator.

Specifications

ManufacturerShenton Group
ModelPHG1500Pe
AvailabilityAvailable; subject to prior sale
ConditionUsed
PricePOA
kVA1360 prime / 1500 standby
Prime output1360 kVA / 1088 kW
Standby output1500 kVA / 1200 kW
Year2024
Hours RunTest Hours Only
EnginePerkins 4012-46TWG3A V12
AlternatorStamford S6L1D-H41
Voltage400 / 230 V
Frequency50 Hz
Phase3
Power factor0.8
Speed1500 rpm
ConfigurationAcoustic / weatherproof enclosure
FuelDiesel
Fuel tank capacity2500 litres
Dry weightApproximately 14,500 kg
Dimensions (L × W × H)Approximately 7000 × 2273 × 2601 mm
Noise levelApproximately 70 dB(A) at 7 metres
Generator serial numberPM24334-19328

Ratings, hours and condition are confirmed in your quotation. Ask our team for any specification that is not listed.

Perkins engine specifications

ManufacturerPerkins
Model4012-46TWG3A
Type4-stroke diesel
ConfigurationV12
DisplacementApproximately 45.5 litres
Bore × stroke160 × 190 mm
AspirationTurbocharged
AftercoolingWater-cooled / JWAC
Cooling systemWater cooled
Fuel systemDirect injection
GovernorElectronic
Rated speed1500 rpm
Starting system24 V DC
Engine identificationU20028K
Rated mechanical outputApproximately 1263 kWm

Stamford alternator specifications

ManufacturerSTAMFORD / Cummins Generator Technologies
ModelS6L1D-H41
Serial numberX24G304721
Continuous alternator rating1400 kVA / 1120 kW
Voltage400 V
Frequency50 Hz
Speed1500 rpm
Phase3
ConnectionStar
Power factor0.80
Rated current2020.8 A
Winding312
Insulation classClass H
Ingress protectionIP23
Temperature rise125 K
Rated ambient temperature40°C
Altitude rating1000 metres
Alternator weightApproximately 2836 kg

This listing uses the supplied specification for the fitted Stamford S6L1D-H41 alternator. Alternator continuous rating and complete generating-set duty ratings are shown separately.

Fuel consumption and tank capacity

50% prime loadApproximately 149 litres/hour
75% prime loadApproximately 212 litres/hour
100% prime loadApproximately 281 litres/hour
Integral tank capacity2500 litres
Operation at 75% loadApproximately 11.5 hours, subject to operating conditions

Approximate manufacturer figures supplied for this listing. Actual consumption and runtime depend on load, operating conditions and usable fuel capacity.

Electrical output

Prime power1360 kVA / 1088 kW
Standby power1500 kVA / 1200 kW
Approximate prime current at 400 V1963 A
Approximate standby current at 400 V2165 A

Prime power is intended for extended operation with varying loads. Standby power is intended for emergency operation during mains failure. Confirm the required duty and site loading with FW Power.

Delivery & options

UK delivery or collection

Tell us your postcode and whether you can offload the generator. We can quote for suitable transport, including Hiab delivery where required, or arrange collection from our Cheshire yard.

Worldwide export

Delivery is quoted separately. Send the final destination and your handling requirements so we can discuss transport and shipping.

Installation & support

Ask about installation and commissioning, automatic transfer switches and ongoing servicing for your application.

Generator photos

Let’s put your power in place.

Tell us what you need to power. We’ll help you find the right solution.

Talk to our team